S-0-0217 parameter set preselection – BECKHOFF AX5000 S-IDN Parameters User Manual

Page 141

Advertising
background image

S­IDNs

S­0­0217 Parameter set preselection

The parameter specifies which data set 0 ­ 7 is activated with the command S­0­0216.

Attributes

Name

Value

Format

udec

Data length

16

Decimal point

0

Min value

0

Max value

7

Default value

­

Unit

­

Changeable in EtherCAT state

PreOp, SafeOp, Op

Cyclic transfer

No

Device parameter

No

Related to interface revision

from 200

If the parameter does not enable parameter set switchover, the drive only accepts data set 0. Data set 0
must exist in each drive. This data set is activated during initialisation.

Bit patterns

Bit Meaning

0 ­2 Parameter set preselection

Parameter set preselection for parameter set switchover

0 = Parameter set 0 
Data set 0

1 = Parameter set 1 
Data set 1

2 = Parameter set 2 
Data set 2

3 = Parameter set 3 
Data set 3

4 = Parameter set 4 
Data set 4

5 = Parameter set 5 
Data set 5

6 = Parameter set 6 
Data set 6

7 = Parameter set 7 
Data set 7

3 ­

15

Reserved

Note

IDNs involved

S‐0‐0216 [

}

 140]

AX5000 ­ IDN­Descriptions

141

Version 3.1