Variable names, 6 homing, Homing -46 – Lenze EVS93xx CrossCutter User Manual

Page 60: Cross cutter, Features of the "cross cutter" prepared solution

Advertising
background image

Cross Cutter

Features of the "Cross Cutter" prepared solution



Prepared Solution Servo PLC / ECSxA 1.1 EN

2-46

Variable

names

Possible settings:

Code

Default

Selection

Comments

C3643/

000

3.0000

0.0001... {0.0001

[s_units]}

... 214748.0000 Following error switch-off threshold

C3644/

000

0.5000

0.0001... {0.0001

[s_units]}

... 214748.0000 Following error hysteresis

C3645/

000

1.5000

0.0001... {0.0001

[s_units]}

... 214748.0000 Following error warning limit

C3646/

000

0.5000

0.0001... {0.0001

[s_units]}

... 214748.0000 Following error warning limit hysteresis

2.5.6 Homing

This function can be used to perform homing. The drive moves in a preselected mode and
calculates the zero position (home) automatically on the basis of a home mark before declaring
this value to the drive control. All position data refers to this home position.

Homing is generally

performed once following mains connection.
The following can be used as home mark signals:
• Zero pulse (signal edge from encoder system for position actual value, one per

motor revolution)

• Touch probe (signal edge at corresponding touch-probe input of PLC)

• A preliminary stop position can be set via a homing switch. In this case, home will be the

next zero position of the actual value encoder on the motor or the next touch probe
(depending on the selected mode).

Figure 11: Control signals for homing