Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

103

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

OutNetFaultValue

This parameter determines the state of the
starter outputs when an Ethernet fault
occurs and Parameter 54
(OutNetFaultState) is set to 0.
0 = OFF
1 = ON

Parameter Number

55

Access Rule

GET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutNetIdleState

This parameter in conjunction with
Parameter 57 (OutNetIdleValue) defines
how the starter outputs will respond when
a network is idle.
0 = GoToIdleValue
1 = HoldLastState

Parameter Number

56

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutNetIdleValue

This parameter determines the state that
starter outputs assumes when the
network is idle and Parameter 56
(OutNetIdleState) is set to 0.
0 = OFF
1 = ON

Parameter Number

57

Access Rule

GET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Input00Function

This parameter determines the special
function for User Input 0:
0 = NoFunction
1 = FaultReset
2 = MotionDisable➊
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease➊

➊ These choices are level sensitive. All
others are edge sensitive

Parameter Number

58

Access Rule

GET/SET

Data Type

USINT

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

4

Default Value

0