176

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 6

Specifications

Control Circuit
(External Source)

Power Supply

NEC Class 2

Rated Operating Voltage

24V DC (+10%, -20%)

Overvoltage Protection

Reverse-polarity protected

Unswitched Power Supply

Requirements

Voltage

19.2…26.4V DC

Nominal Current

150 mA

Power

3.6 W

Input Current (each) ➊

50 mA

Maximum Current

450 mA

Maximum Power

14.4 W

Peak Inrush ➋

<5 A for 35 ms

Switched Power Supply

Requirements

Voltage

19.2…26.4V DC

Nominal Current

125 mA

Power

3 W

Output Current (each) ➊

500 mA

Maximum Current

1.625 A

Maximum Power

42 W

Peak Inrush ➋

<5 A for 35 ms

Switched and Unswitched

Power Supply Requirements

Voltage

19.2…26.4V DC

Nominal Current

275 mA

Power

6.6 W

Number of Inputs (x 50 mA)

user defined

Number of Outputs (x 500 mA)

user defined

Maximum Current

275 mA + user defined

Maximum Power

6.6 W + (24V DC x user defined)

Peak Inrush ➋

<10 for 35 ms

Control Circuit
(Internal Source)

An internal 50 W power supply sources 24V DC for input, outputs, and logic control.

Short Circuit
Current Rating
(SCCR)

Cat. No.

Sym. Amps RMS

Circuit Breaker

Fuse

290/1_-*-G1 (or G3)

10 kA @ 480Y/277

When used with Allen Bradley

Cat. No. 140U-D6D3-C30

CC, J, or T fuse

(maximum 45 A)

290/1_-*-G1 (or G3)

5 kA @ 480Y/277

UL Class fuse (maximum 45 A)

290/1_-*-G2

10 kA @ 480Y/277

CC, J, or T fuse

(maximum 40 A)

Short Circuit
Coordination

Type 1

Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications

➊ I/O is configurable to either input or output.

➋ Assumes zero wire resistance. Wire impedance will reduce current inrush.

Electrical Ratings