Advanced configuration – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 143

Advertising
background image

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

143

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

Advanced Configuration

KeypadDisable

This parameter disables all keypad
function except for the “OFF” and “RESET”
buttons.
0 = KeypadEnabled
1 = KeypadDisabled

Parameter Number

67

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

SetToDefaults

This parameter if set to “1” will set the
device to the factory defaults.
0 = NoAction
1 = SetToDefaults

Parameter Number

68

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

AccelTime2

When active, sets the rate of acceleration for all speed increases except for jog.

Parameter Number

69

Related Parameters

36

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

0.0

Maximum Value

600.0

Default Value

20.0

Maximum Freq

Accel Time

--------------------------------------

Accel Rate

=

Parameter 35
(Maximum Freq)

Speed

Accel
Time 2

0

0

Time

Decel
Time 2

Ac

celer

ation

Dec

eler

ation