Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 178

Advertising
background image

178

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 6

Specifications

Environmental Ratings

Operating Temperature Range

-20…+50 °C (-4…+122 °F)

Storage and Transportation Temperature Range

-25...+85 °C (-13…+185 °F)

Altitude 2000

m

Humidity 5…95%

(non-condensing)

Pollution Degree

3

Enclosure Ratings

IP66/UL Type 4/12 ➊

Approximate Shipping Weight

4.6 kg (10 lb)

Mechanical Ratings

Resistance to Shock

Operational

30 G, exceeds IEC 60947-1

Non-Operational

50 G, exceeds IEC 60947-1

Resistance to Vibration

Operational

2.5 G, tested to MIL-STD-810G, exceeds IEC 60947-1

Non-Operational

5 G, tested to MIL-STD-810G, exceeds IEC 60947-1

Disconnect Lock Out

Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp

Disconnect LOTO Locks

Up to 2 locks or hasps are supported

Disconnect Mechanical Life

200 000 operations

Contractor Utilization Category

(IEC)

AC-1, AC-3, AC-4 (refer to Life Load Curves)

Contactor Opening Delay

8…12 ms

Contactor Closing Delay

18…40 ms

Minimum Off Time

200 ms

Contactor Mechanical Life

15 million operations

Power Terminals

Motor Terminals

Control Terminals

PE/Ground

Wire Size

(2) #18 …#10 AWG

(0.8…5.2 mm

2

) per terminal

#18…#10 AWG

(0.8…5.2 mm

2

) per terminal

(2) #18 …#10 AWG

(0.8…5.2 mm

2

) per terminal

(2) #16 …#10 AWG

(1.3…5.2 mm

2

) per terminal

Wire Type

Multi-strand copper wire

Tightening Torque

10.6 ± 2 lb•in (1.2 ± 0.2 N•m)

18 ± 2 lb•in (2 ± 0.2 N•m)

Wire Strip Length

0.35 ± 0.01 in. (9 ± 2 mm)

Power Rating

600V AC/25 Amp VAC

600 V AC/10 Amp VAC

600 V AC/10 Amp VAC

Emission and Immunity Ratings

Emission

Conducted

EN 60947-4-1

Class A

Radiated

Electrostatic Discharge

4 kV contact, 8 kV air

Radio Frequency Electromagnetic Field

EN 60947-4-1

10V/m, 80 MHz…1 GHz
10V/m, 1.4 GHz…2 GHz

Immunity

Fast Transient

2 kV (Power)

2 kV (PE)

1 kV (Communication and control)

Surge Transient

1 kV (12)

L-L

, 2 kV (2)

L-N

(earth)

Radio Frequency Conducted Disturbance

10V, 150 kHz…80 MHz

➊ IP66/UL Type 4 is available with gland options G1-3. IP66/UL Type 4/12 available with G1 and G3 gland option