Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 150

Advertising
background image

150

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 4

Bulletin 290D/291D/294D Programmable Parameters

AutoRstrtDelay

Sets time between restart attempts when
Parameter 84(Auto Rstrt Tries) is set to a
value other than zero.

Parameter Number

85

Related Parameter

84

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

0.0

Maximum Value

120.0

Default Value

1.0

BoostSelect

Sets the boost voltage (% of Parameter 28
[MotorNPVolts]) and redefines the Volts
per Hz curve.

See Table 21 for details.

Parameter Number

86

Related Parameters

28, 29

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

Minimum Value

1

Maximum Value

14

Default Value

8

Table 21 - Boost Select Options

Options

Description

Custom V/Hz

Variable Torque

(Typical fan/pump curves)

1

30.0, VT

2

35.0, VT

3

40.0, VT

4

45.0, VT

5

0.0 no IR

Constant Torque

6

0.0

7

2.5, CT

8

5.0, CT (default)

9

7.5, CT

10

10.0, CT

11

12.5, CT

12

15.0, CT

13

17.5, CT

14

20.0, CT

Advertising