Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

107

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

JamTripDelay

This parameter determines how much
time above the Jam Level before the unit
will trip.

Parameter Number

71

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

1

Maximum Value

25.0

Default Value

5.0

JamTripLevel

This parameter determines the Jam Trip
Level as a percentage of Full Load Amps.

Parameter Number

72

Access Rule

GET

Data Type

UINT

Group

Advanced Config.

Units

%FLA

Minimum Value

50

Maximum Value

600

Default Value

250

JamWarningLevel

This parameter determines the Jam
Warning Level as a percentage
of Full Load Amps.

Parameter Number

73

Access Rule

GET

Data Type

UINT

Group

Advanced Config.

Units

%FLA

Minimum Value

50

Maximum Value

600

Default Value

150

StallEnabledTime

This parameter determines the time
that stall detection is enabled during
motor starting.

Parameter Number

74

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

secs

Minimum Value

0

Maximum Value

250

Default Value

10