StallTripLevel

This parameter determines the Stall Trip
Level as a percentage of Full Load Amps.

Parameter Number

75

Access Rule

GET

Data Type

UINT

Group

Advanced Config.

Units

%FLA

Minimum Value

100

Maximum Value

600

Default Value

600

ULInhibitTime

This parameter determines the time
during motor starting that Underload
detection is inhibited.

Parameter Number

76

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

secs

Minimum Value

0

Maximum Value

250

Default Value

10

ULTripDelay

This parameter determines the time below
Underload Level before the unit will trip.

Parameter Number

77

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

1

Maximum Value

25.0

Default Value

5.0

ULTripLevel

This parameter determines the
Underload Trip Level as a percentage
of Full Load Amps.

Parameter Number

78

Access Rule

GET

Data Type

USINT

Group

Advanced Config.

Units

%FLA

Minimum Value

10

Maximum Value

100

Default Value

50