Clear a type 1 fault and restart the drive – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 149

Advertising
background image

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

149

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

Figure 37 - Overload Trip Curves

Clear a Type 1 Fault and Restart the Drive

1.

Set Parameter 84 (AutoRestartTries) to a value other than 0.

2.

Set Parameter 85 (AutoRestartDelay) to a value other than 0.

Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault without Restarting the Drive

1.

Set Parameter 84 (AutoRestartTries) to a value other than 0.

2.

Set Parameter 85 (AutoRestartDelay) to 0.

Min. Derate

0

80

100

60

40

20

% of Motor Overload Current (P30)

No Derate

0

80

100

60

40

20

% of Motor Nameplate Hertz (P29)

% of Motor Overload Current (P30)

% of Motor Nameplate Hertz (P29)

% of Motor Overload Current (P30)

% of Motor Nameplate Hertz (P29)

Max. Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

SWCurrentTrip

Enables/disables a software instantaneous
(within 100 ms) current trip.

For 0.5 Hp units – Min = 0; Max = 3.0; Default = 0
For 1.0 Hp units – Min = 0; Max = 5.0; Default = 0
For 2.0Hp units – Min = 0; Max = 8.4; Default = 0

Parameter Number

83

Related Parameter

30

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x Amps

Minimum Value

0.0

Maximum Value

Hp Dependent

Default Value

0.0 (Disabled)

AutoRstrtTries

Set the maximum number of times the drive
attempts to reset a fault and restart.

Parameter Number

84

Related Parameter

85

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

Minimum Value

0

Maximum Value

9

Default Value

0

ATTENTION: Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use this function
without considering applicable local, national, and international codes,
standards, regulations, or industry guidelines.

Advertising