Chapter 4

Bulletin 290D/291D/294D Programmable Parameters

DCBrakeTime

Sets the length of time that DC brake current is
injected into the motor. Refer to Parameter 76
(DCBrakeLevel).

Parameter Number

75

Related Parameters

32, 76

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x secs

Minimum Value

0.0

Maximum Value

99.9

(Setting of 99.9 = Continuous)

Default Value

0.0

DCBrakeLevel

Defines the maximum DC brake current, in amps,
applied to the motor when Parameter 32
(StopMode) is set to either
0 = RAMP or 2 = DC BRAKE.

For 0.5 Hp units – Min = 0; Max = 2.7; Default = .1
For 1.0 Hp units – Min = 0; Max = 4.5; Default = .1
For 2.0Hp units – Min = 0; Max = 7.5; Default = .2

Parameter Number

76

Related Parameters

32, 75

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Config.

Units

x.x Amps

Minimum Value

0.0

Maximum Value

Hp Dependant

Default Value

Hp Dependant

ATTENTION:

If a hazard of injury due to movement of equipment or material exists, an

auxiliary mechanical braking device must be used.

This feature should not be used with synchronous or permanent magnet

motors. Motors may be demagnetized during braking.

Time

[DC Brake Level]

[DC Brake Time]

Stop Command

Speed

Voltage

Volts Speed

[DC Brake Level]

[DC Brake Time]

Time

Voltage

Speed

Stop Command

Volts Speed

DC Injection Braking Mode

Ramp-to-Stop Mode

}

}

}

}