Specifications

Chapter 6

Environmental Ratings

Operating Temperature Range

-20…+40 °C (-4…+104 °F)

50 °C (122 °F) without derating, when properly rated line reactors are installed

in branch circuit.

Storage and Transportation

Temperature Range

–25...+85 °C (–13…+185 °F)

Altitude

1000 m

Humidity

5…95% (non-condensing)

Pollution Degree

3

Enclosure Ratings

IP66/UL Type 4/12 ➊

Approximate Shipping Weight

7.3 kg (16 lb)

➊ IP66/UL Type 4 is available with gland options G1-3. IP66/ UL Type 4/12 available with G1 and G3 gland option.

Mechanical Ratings

Resistance to Shock

Operational

30 G (exceeds IEC 61800-5-1)

Non-Operational

50 G (exceeds IEC 61800-5-1)

Resistance to Vibration

Operational

2.5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)

Non-Operational

5 G, MIL-STD-810G, (exceeds IEC 61800-5-1)

Disconnect Lock Out

Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp

Disconnect LOTO Locks

Up to 2 locks or hasps are supported

Disconnect Mechanical Life

200 000 operations

Power Terminals

Motor Terminals

Control Terminals

PE/Ground

Source Brake

Wire Size

(2) #18 …#10 AWG

(0.8…5.2 mm

2

) per

terminal

#18…#10 AWG

(0.8…5.2 mm

2

) per

terminal

(2) #18 …#10 AWG

(0.8…5.2 mm

2

) per

terminal

(2) #16 …#10 AWG

(1.3…5.2 mm

2

) per

terminal

#16 …#10 AWG

(1.0…4.0 mm

2

) per

terminal

Wire Type

Multi-strand copper wire

Tightening Torque

10.6 ± 2 lb•in (1.2 ± 0.2 N•m)

18 ± 2 lb•in

(2 ± 0.2 N•m)

4.8 ± 2 lb•in

(0.5 ± 0.2 N•m)

Wire Strip Length

0.35 ± 0.01 in. (9 ± 2 mm)

Power Rating

600V AC/25 Amp VAC

600V AC/10 Amp VAC

600V AC/10 Amp VAC

600V AC/10 Amp VAC

Emission and Immunity Ratings

Emission

Conducted

EN 55011

Class Group 2

Radiated

Electrostatic Discharge

4 kV contact, 8 kV air

Radio Frequency Electromagnetic Field

EN 61800-3

10V/m, 80 MHz…1 GHz

Immunity

Fast Transient

2 kV (Power)

2 kV (PE)

1 kV (Communication and control)

Surge Transient

1 kV (12)

L-L

, 2 kV (2)

L-N

(earth)

Radio Frequency Conducted Disturbance

10V, 150 kHz…80 MHz

Advertising