Identity object, Class code 0x0001 – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 205

Advertising
background image

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

205

CIP Information

Appendix B

Identity Object

CLASS CODE 0x0001

The following class attributes are supported for the Identity Object:

One instance of the Identity Object will be supported for Bulletin 290D and Bulletin
291D; 2 for Bulletin 294D. The following table shows what each instance will represent.

Each instance of the Identity Object will contain the following attributes:

➊ See product code definitions in

Table 29

, Product Codes and Name Strings.

Extended Device Status Field (bits 4-7) in “Status” Instance Attribute 5.

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

1

2

Get

Max Instance

UINT

1 for DOL/Reverser; 2 for VFD

Instance

Name

Revision Attribute

1

Main Control Board

The firmware rev of the main control board operating system

2

PowerFlex 4M (294D only)

The firmware revision of the PowerFlex 4M

Attribute ID

Access Rule

Name

Data Type

Value

1 Get

Vendor

UINT

1

2 Get

Device

Type

UINT

22

3

Get

Product Code

UINT

Product Code specific.

4 Get

Revision

Major Revision
Minor Revision

Structure of:

USINT
USINT

5 Get

Status

WORD

Bit 0 - 0 = Not Owned; 1 = Owned by Master
Bit 2 - 0 = Factory Defaulted; 1 = Configured
Bits 4-7 – Extended Status (see table below)
Bit 8 - Minor Recoverable fault
Bit 9 - Minor Unrecoverable fault
Bit 10 - Major Recoverable fault
Bit 11 - Major Unrecoverable fault

6

Get

Serial Number

UDINT

Unique number for each device

7

Get

Product Name

String Length
ASCII String

Structure of:

USINT
STRING

Product Code specific

8

Get

State

USINT

Returns the value 3 = Operational

9 Get

Configuration
Consistency Value

UINT

Unique value depending on output of the parameter
checksum algorithm.

102

Get

Build

UDINT

Firmware Build Number

Value

Description

0

Self-testing or unknown

1

Firmware update in progress

2

At least one faulted I/O connection

3

No I/O connections established

Advertising