Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 137

Advertising
background image

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

137

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

ProtectFltReset

This parameter resets a Protection Fault
by setting the bit to 1.
0 = NoAction
0 > 1 = ResetFault

Parameter Number

44

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

RunNetFltAction

This parameter in conjunction with
Parameter 46 (RunNetFltValue) defines
how the starter will respond when a
network fault occurs as determined.
0 = GoToFaultValue
1 = HoldLastState

Parameter Number

45

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

RunNetFltValue

This parameter determines how the starter
will be commanded in the event of a fault.
State the starter will go to on a NetFlt if
Parameter 45 (RunNetFltAction) = 1
(GotoFault-Value).
0 = OFF
1 = ON

Parameter Number

46

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

RunNetIdlAction

This parameter in conjunction with
Parameter 48 (RunNetIdlValue) defines
how the starter will respond when
a network is idle as determined
by Parameter 48.
0 = GoToIdleValue
1 = HoldLastState

Parameter Number

47

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Advertising