Motor and control group – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 131

Advertising
background image

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

131

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

Motor and Control Group

SnapShotOutVolts

This parameter provides a snapshot
of output voltage at time of last trip.

Parameter Number

25

Access Rule

GET

Data Type

UINT

Group

Trip Status

Units

x.x V AC

Minimum Value

0

Maximum Value

999.9

Default Value

0

SnapShotBusVolts

This parameter provides a snapshot of DC
bus voltage level at time of last trip.

Parameter Number

26

Access Rule

GET

Data Type

UINT

Group

Trip Status

Units

V DC

Minimum Value

0

Maximum Value

1200

Default Value

0

SnapShotDrvTemp

This parameter provides a snapshot of
operating temperature at time of last trip.

Parameter Number

27

Access Rule

GET

Data Type

UINT

Group

Trip Status

Units

°C

Minimum Value

0

Maximum Value

9999

Default Value

0

MotorNPVolts

Set to the motor nameplate rated voltage.

Parameter Number

28

Access Rule

GET/SET

Data Type

UINT

Group

Motor and Control

Units

V AC

Minimum Value

35

Maximum Value

460

Default Value

460

O

Stop drive before changing this
parameter.

Advertising