Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

97

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

Basic Configuration Group

SnapShotLAvgAmps

This parameter provides a snapshot of
average of 3 Phase currents at time
of last trip.

Parameter Number

26

Access Rule

GET

Data Type

INT

Group

Trip Status

Units

x.xx Amps

Minimum Value

0

Maximum Value

32767

Default Value

0

SnapShot%Thermal

This parameter provides a snapshot of the
percentage of Thermal Capacity used at
time of last trip.

Parameter Number

27

Access Rule

GET

Data Type

USINT

Group

Trip Status

Units

Percent

Minimum Value

0

Maximum Value

100

Default Value

0

FLASetting

The motor’s full load current rating is
programmed in this parameter.

Parameter Number

28

Access Rule

GET/SET

Data Type

INT

Group

Basic Configuration

Units

x.xx Amps

Minimum Value

See Table 20.

Maximum Value

See Table 20.

Default Value

See Table 20.

Table 20 - FLA Setting Ranges and Default Values (with indicated setting precision)

FLA Current Range (A)

Default Value

460V AC

Minimum Value

Maximum Value

290D/1_-FA_*

3 Hp

0.24

3.5

0.24

290D/1_-FB_*

5 Hp

1.1

7.6

1.1