Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

217

CIP Information

Appendix B

Multiple instances of the Connection Object will be supported, instances 1, 2,
and 4 from the group 2 predefined master/slave connection set, instances 5-7 will
be available explicit UCMM connections, and instances 8-11 will act as ZIP
consumers.

Instance 1

Instance 1 is the Predefined Group 2 Connection Set Explicit Message
Connection. The following instance 1 attributes will be supported:

Instance 2

Instance 2 is the Predefined Group 2 Connection Set Polled I/O Message
Connection. The following instance 2 attributes will be supported:

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0=nonexistant
1=configuring
3=established
4=timed out

2

Get

Instance Type

USINT

0=Explicit
Message

3

Get

Transport Class Trigger

USINT

0x83 - Server, Transport
Class 3

4

Get

Produced Connection ID

UINT

10xxxxxx011
xxxxxx=node address

5

Get

Consumed Connection ID

UINT

10xxxxxx100
xxxxxx=node address

7

Get

Produced Connection Size

UINT

0x61

8

Get

Consumed Connection Size

UINT

0x61

9

Get/Set

Expected Packet Rate

UINT

in milliseconds

12

Get

Watchdog Action

USINT

01 = auto delete
03 = deferred delete

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

State

USINT

0=nonexistant
1=configuring
3=established
4=timed out

2

Get

Instance Type

USINT

1=I/O Connection

7

Get

Produced Connection Size

UINT

0 to 8

8

Get

Consumed Connection Size

UINT

0 to 8