Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

49

Installation and Wiring

Chapter 2

Figure 19 - On-Machine Stop Stations

ArmorConnect Cable Ratings

The ArmorConnect Power Media cables are rated per UL Type TC 600V 90°C
Dry 75°C Wet, Exposed Run (ER) or MTW 600V 90°C or STOOW 105°C
600V - Canadian Standards Association (CSA) STOOW 600V FT2.
For additional information regarding ArmorConnect Power Media refer
to ArmorStart LT selection guide, publication 290-SG001.

Branch Circuit Protection Requirements for ArmorConnect
Three-Phase Power Media

When using ArmorConnect Three-Phase Power Media, fuses or circuit breakers
may be used for the motor branch circuit ground fault protection if properly
sized and allowed by product labeling.

Circuit Breaker:

Where ArmorStart LT is used with ArmorConnect — suitable for use on a
circuit capable of delivering not more than 10 000 RMS Symmetrical Amperes
at 480Y/277V AC maximum when protected by Cat. No. 140U-D6D3-C30
circuit breaker, refer to the

Specifications

,

Chapter 6

.

IMPORTANT

See the On-Machine Connectivity catalog for specific Ethernet
media components

Enclosure

Type

Quick Connect

Knockout

Type

Operator

Illumination

Voltage

Contact

Configuration

Cat. No.

Plastic

Mini Receptacle

Metric

Twist to Release

24V AC/DC

1 N.C./1 N.O.

800F-1YMQ4

Metal

24V AC/DC

800F-1MYMQ4