Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

75

Product Commissioning

Chapter 3

System Configuration

Selection of produced and consumed I/O assemblies (sometimes referred to as
input and output assemblies) define the format of I/O message data that is
exchanged between the ArmorStart and other devices on the network. The
consumed information is generally used to command the state of its outputs, and
produced information typically contains the state of the inputs and the current
fault status of the device.

The default consumed and produced assemblies are shown below; for additional
formats refer to Appendix B. The ArmorStart default configuration varies
depending on the type of starter.

Choosing the size and format of the I/O data that is exchanged by the
ArmorStart is done by choosing a consumed assembly instance number. This
instance number is written to the

Consumed IO Assy parameter. The different

instances/formats allow user programming flexibility and network optimization.

IMPORTANT

The Consumed and Produced IO Assy parameter values can not be changed
while the ArmorStart is online with a scanner. Any attempts to change the
value of this parameter while online with a scanner will result in the error
message “Object State Conflict”.