Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

153

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

OptionMatch

If product options do not match value, a
hardware fault will occur.

Parameter Number

92

Access Rule

GET/SET

Data Type

DWORD

Group

Advance Config

Units

Minimum Value

0

Maximum Value

0xffffffff

Default Value

0

Bit

Function

4-31

3

2

1

0

— — —

X

KeypadPreesent

— —

X

KeypadNotPresent

X

— —

BrakePresent

X

— — —

BrakeNotPresent

X

— — — —

Reserved

AutobaudEnable

Autobaud enabled when set
0=Disable
1=Enable

Parameter Number

100

Access Rule

SET

Data Type

BOOL

Group

Network

Units

Minimum Value

0

Maximum Value

1

Default Value

1

ConsumedIOAssy

Selects the format of the I/O data
consumed
294 default = 154

Parameter Number

101

Access Rule

SET

Data Type

USINT

Group

Network

Units

Minimum Value

3

Maximum Value

154

Default Value

154