Discrete output point object, Class code 0x0009 – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 220

Advertising
background image

220

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Appendix B

CIP Information

The following common services will be implemented for the Discrete Input Point
Object:

Discrete Output Point
Object

CLASS CODE 0x0009

The following class attributes will be supported for the Discreet Output Point
Object:

fo

Eight instances of the Discrete Output Point Object will be supported for DOL/
Reverser (Bulletin 290D/291D) units. Ten instances will be supported for Drive
(Bulletin 294E) units. The following table summarizes the DOP instances:

Service Code

Implemented for:

Service Name

Class Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Attribute ID

Access Rule

Name

Data Type

Value

1 Get

Revision

UINT

1

2

Get

Max Instance

UINT

8 for 290D/291D, 10 for 294D

Instance Name

Alternate

Mapping

Description

1

Run Fwd Output

0029-01-03

Run Forward output.

2

Run Rev Output

0029-01-04

Run Reverse output.

3

User Output A

None

These are the six possible user outputs for all starter types. Their fault/idle
behavior is defined in DOP Instance 3.

4

User Output B

None

5

User Output C

None

6

User Output D

None

7

User Output E

None

8

User Output F

None

9

Drive Jog Fwd

None

This instances exists for Inverter (Bulletin 294D) units only.

10

Drive Jog Rev

None