Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 4

Bulletin 290D/291D/294D Programmable Parameters

ConsumedIOAssy

Selects the format of the I/O data
consumed
290 default = 150

Parameter Number

101

Access Rule

SET

Data Type

USINT

Group

Network

Units

Minimum Value

3

Maximum Value

150

Default Value

150

ProducedIOAssy

Selects the format of the I/O data
consumed
290 default = 151

Parameter Number

102

Access Rule

SET

Data Type

USINT

Group

Network

Units

Minimum Value

52

Maximum Value

151

Default Value

151

AutoRunZip

Enables this device to produce COS
messages on powerup
0=Disable
1=Enable

Parameter Number

103

Access Rule

SET

Data Type

BOOL

Group

ZIP

Units

Minimum Value

0

Maximum Value

1

Default Value

0

ZoneProducedEPR

Expected Packet Rate for producing Zip
COS connection

Parameter Number

104

Access Rule

SET

Data Type

UINT

Group

ZIP

Units

msec

Minimum Value

1

Maximum Value

65535

Default Value

75