Recommended cord grips, Shield terminating connectors – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 61

Advertising
background image

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

61

Installation and Wiring

Chapter 2

Recommended Cord Grips

The following are recommended cord grips to be used
for ArmorStart LT installations.

Table 9 - Cord grip for Motor, Power, and Control
Recommended Thomas and Betts Cord Grips for G1 and G3 Glands.

Shield Terminating Connectors

The cable connector selected must provide good 360

o

contact and low transfer

impedance from the shield or armor of the cable to the conduit entry plate at
both the motor and the ArmorStart LT for electrical bonding. SKINTOP

®

MS-SC/MS-SCL cable grounding connectors and NPT/PG adapters from
LAPPUSA are good examples of this type of shield terminating gland.

Description

Gland

Knockout

Size

Cable Diameter Range (in.

2

)

Thomas and Betts Part Nos.

Cord Grip

Sealing

Ring

Lock Nut

Motor/Source Brake

G1

0.75 in.

0.500…0.750

2932NM

5263

142TB

Motor/Source Brake

G1

0.75 in.

0.660…0.780

2675

5263

142TB

Power

G1

1.0 in.

0.660…0.780

2676

5264

143

Power

G1

1.0 in.

0.770…0.895

2677

5264

143

Control Power, Motor/Source
Brake

G3

M20

0.236…0.473

CC-ISO20-G

GMN-M20

3-Phase Power

G3

M25

0.512…0.709

CC-ISO25-G

GMN-M25

Advertising