Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 4

Bulletin 290D/291D/294D Programmable Parameters

Starter Protection Group

OLResetLevel

This parameter determines the % Thermal
Capacity which an overload can be cleared.

Parameter Number

29

Access Rule

GET/SET

Data Type

BYTE

Group

Basic Configuration

Units

% TCU

Minimum Value

75

Maximum Value

100

Default Value

75

OverloadClass

This parameter provides the overload trip
classification.
1 = 10
2 = 15
3 = 20

Parameter Number

30

Access Rule

GET

Data Type

USINT

Group

Basic Configuration

Units

Minimum Value

1

Maximum Value

3

Default Value

1

ProtFltResetMode

This parameter configures the Protection
Fault reset mode.
0 = Manual
1 = Automatic

Parameter Number

41

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

ProtectFltEnable

This parameter enables or disables
protection faults (not all faults can be
disabled).

Parameter Number

42

Access Rule

GET

Data Type

WORD

Group

Trip Status

Units

Minimum Value

0

Maximum Value

0xE3BF

Default Value

0