Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 184

Advertising
background image

184

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 6

Specifications

Input and Output Ratings

Input

Supply Voltage

Unswitched power A3/A2

Type of Inputs

24V DC current sinking

Connection Type

Single keyed M12, quick disconnect

Input per Connection

1/each

Rated Operating Voltage

24V DC

On-State Input Voltage (pin 4)

10…26.4V DC, nominal 24V DC

Off-State Input Voltage

5V DC

On-State Input Current (pin 4)

1…3.7 mA, nominal 2.6 mA @ 24V DC

Off-State Input Current

<1.5 mA

Maximum Sensor Leakage Current

<2.5 mA

Maximum Number of Input Devices

6

Maximum Sensor Sourcing Current (pin 1)

50mA per point (max 300mA total for sourcing one device)

Sensor Operating Voltage Range

19.2…26V DC

Input Bounce Filter ➊

(Software Configurable)

Off-On or On-Off: 0.5 ms + 64 ms

Filtering

100 μs

DeviceLogix I/O Response

2 ms (500 Hz)

Output

Supply Voltage (Switched Power)

A1/A2

Type of Outputs

DC sourcing

Load Types

Resistive or light inductive

Utilization Category (IEC)

DC-1, DC-13

Output State

Normally Open (N.O.)

Connection Type

Single keyed M12, quick disconnect

Output per Connection

1/each

Overcurrent Protection ➋

1.5 A (the sum of all outputs cannot exceed this value)

Rated Insulation Voltage (U

i

)

UL: 1500V AC, IEC: 2000V AC

Rated Operating Voltage (U

e

)

19.2…26.4V DC

Maximum Blocking Voltage

35V DC

Nominal Operating Current (I

e

)

500 mA per point

Maximum Thermal Current (I

the

)

500 mA per point

Maximum Off-state Leakage Current

1 μA

Maximum Number of Outputs

6

Surge Suppression

Integrated diode to protect against switching loads

➊ Input ON-to-OFF delay time is the time from a valid input signal to recognition by the module.

➋ If an output exceeds 1.5 A for greater than 7 ms, a fault is generated