Electromagnetic
Compatibility (EMC)

The following guidelines are provided for EMC installation compliance.

General Notes (Bulletin 294D only)

The motor cable should be kept as short as possible in order to avoid
electromagnetic emissions as well as capacitive currents. CE conformity
of ArmorStart LT with EMC directive does not guarantee the entire
machine installation complies with CE EMC requirements. Many
factors can influence total machine/installation compliance.

The EMI filter may result in relatively high ground leakage currents.
Therefore, ArmorStart LT must only be applied in installations that are
solidly grounded (bonded) to the building power distribution ground.

U (T1)

V (T2)

W (T3)

PE

One or More

Ground Leads

Braid wires pulled back in a 360

° pattern

around the ground cone of the connector

Drain wires pulled back in a 360

° pattern

around the ground cone of the connector

Metal locknut bonds the

connector to the panel

Metal connector body

makes direct contact with

the braid wires

ATTENTION: Shielded connector or motor cable is mandatory for CE compliant
installations.

Ground Bushing