Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 197

Advertising
background image

197

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

197

Applying More Than One ArmorStart LT Motor Controller in a Single Branch Circuit on Industrial Machinery

Appendix A

1. Requirement One: Controller Ratings

— The motor controllers and

overload relays must be listed for group installation with specified maximum
branch-circuit protection.

Text:

“7.2.10.4(1) Each motor controller and overload device is… listed for group

installation with specified maximum branch-circuit protection…”

Analysis:

To apply the ArmorStart LT motor controllers in the multiple-motor

branch circuit shown in

Figure 43

, 7.2.10.4(1) must be satisfied; each controller

must be listed for group installation with specified maximum branch-circuit
protection. The UL listing for each ArmorStart LT motor controller confirms
that it – including its integral overload relay and motor disconnecting means — is
suitable for motor group installation with specified fuses, satisfying 7.2.10.4(1).
The Bulletin 290D and 291D controllers are listed for group installation
according to UL 508, Industrial Control Equipment. The Bulletin 294D
controllers are listed for group installation according to UL 508C, Power
Conversion Equipment.

Referring to

Figure 44

(a) indicates the markings on the nameplate that satisfy

7.2.10.4(1). The marking “Suitable for Motor Group Installation” satisfies the
requirement to be listed for group installation. The ratings located beneath the
description “Max. Ratings” are the specified maximum branch circuit protection.
The (a) beside the fuse(s) indicates that the maximum protection specified on the
nameplate applies to these fuse(s).

2. Requirement Two: Conductor Short-circuit and Ground-Fault
Protection

— The fuse must protect the conductors for short-circuit faults

and ground faults.

Text:

“7.2.10.4(2) The rating or setting of the branch short-circuit and ground-

fault protection device does not exceed the values in

Table 27

for the smallest

conductor in the circuit.”

Analysis:

Referring to

Figure 43

, 7.2.10.4(2) must be satisfied. The fuse, as

indicated by the description in

Figure 43

(a), is the branch short-circuit and

ground-fault protection device. The word circuit means the branch circuit.
The conductors of the branch circuit start at the load side of the fuses and end
at the input to the motor, including the conductors between the motor
controllers and the motor. The smallest conductor in the circuit is any one
of the 14 AWG conductors that supply each controller and motor. The note
at (b) indicates the conductor protection is based on the smallest conductor,
14 AWG. Referring to

Table 27

a 14 AWG conductor may be used in a circuit

that is protected by a fuse of any class having a rating of 60 amperes or less (c).
Therefore, selecting a fuse of any class with a maximum rating of 60 amperes
satisfies the conductor protection requirement of 7.2.10.4(2).

Supplementary Note 1:

The value specified in

Table 27

is the maximum rating

of fuse that 7.2.10.4(2) permits to protect that size of conductor. The rating of
the fuse may be set to the maximum value given by

Table 27

for the smallest

conductor without further justification. However, if any controller, or other
component, has a maximum rating of fuse that is less than the

Table 27

value, the

Advertising