Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 68

Advertising
background image

68

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Chapter 3

Product Commissioning

Figure 34 - Network Address Example

The switch value of 88 allows the user to reset to factory default configuration
including configuration parameters. This setting is useful in situations where the
user wishes to decommission a module or when the user wishes to commission a
previously-used module that has an unknown configuration. When the switches
are set to 888, upon the next power cycle the ArmorStart LT will return to
factory default settings and cease all communications. The Module Status LED
shall transition to blinking red and the Network Status LED shall transition
to off.

After reset, the user will then need to change the IP address to a valid setting and
power cycle. The purpose of this is to prevent the user from resetting the module
and then never changing the switch setting from 88.

This example shows the
node address set to 00.

IMPORTANT

Setting the node address to “88” followed by a power cycle will reset the device to its factory default configuration.
To resume network communication the address MUST be set to a valid address and power cycled again.