Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 154

Advertising
background image

154

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 4

Bulletin 290D/291D/294D Programmable Parameters

ProducedIOAssy

Selects the format of the I/O data
consumed
294 default = 155

Parameter Number

102

Access Rule

SET

Data Type

USINT

Group

Network

Units

Minimum Value

52

Maximum Value

190

Default Value

155

AutoRunZip

Enables this device to produce COS
messages on powerup
0=Disable
1=Enable

Parameter Number

103

Access Rule

SET

Data Type

BOOL

Group

ZIP

Units

Minimum Value

0

Maximum Value

1

Default Value

0

ZoneProducedEPR

Expected Packet Rate for producing Zip
COS connection

Parameter Number

104

Access Rule

SET

Data Type

UINT

Group

ZIP

Units

msec

Minimum Value

1

Maximum Value

65535

Default Value

75

ZoneProducedPIT

Production Inhibit Time for the producing
Zip connection

Parameter Number

105

Access Rule

SET

Data Type

UINT

Group

ZIP

Units

msec

Minimum Value

1

Maximum Value

65535

Default Value

75

Advertising