Chapter 4
Bulletin 290D/291D/294D Programmable Parameters
Figure 35 - S Curve
DecelTime1
Sets the rate of deceleration for all speed decreases.
Parameter Number
37
Related Parameters
33, 36
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
x.x secs
Minimum Value
0.1
Maximum Value
600.0
Default Value
10.0
Maximum Freq
Decel Time
--------------------------------------
Decel Rate
=
Parameter 35
(Maximum Freq)
Speed
Accel
Time 1
0
0
Time
Decel
Time 1
Ac
celer
ation
Dec
eler
ation
SCurvePercent
Sets the percentage of acceleration or
deceleration time that is applied to ramp
as S Curve. Time is added, half at the
beginning and half at the end of the ramp.
Parameter Number
38
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
Percentage
Minimum Value
0
Maximum Value
100
Default Value
0
Example:
Accel Time = 10 Seconds
S Curve Setting = 50%
S Curve Time = 10 x 0.5 = 5 Seconds
Total Time = 10 + 5 = 15 Seconds
1/2 S Curve Time
2.5 Seconds
Total Time to Accelerate = Accel Time + S Curve Time
Accel Time
10 Seconds
50% S Curve
Target 2
Target
1/2 S Curve Time
2.5 Seconds
JogFrequency
Sets the output frequency when the jog
command is issued.
Parameter Number
39
Related Parameters
35, 40
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
x.x Hz
Minimum Value
0.0
Maximum Value
400.0
Default Value
10.0