Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

FilterOnOff

This parameter determines the input
(which must be absent for this time)
before being reported OFF.

Parameter Number

51

Access Rule

GET/SET

Data Type

USINT

Group

User I/O Config.

Units

msecs

Minimum Value

0

Maximum Value

64

Default Value

0

OutProtFltState

This parameter in conjunction with
Parameter 53 (OutProtFltValue) defines
how the starter outputs will respond
when a fault occurs.
0 = GoToPrFltValue
1 = IgnorePrFlt

Parameter Number

52

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutProtFltValue

This parameter determines how the starter
outputs will be commanded in the event
of a protection fault if Parameter 52
(OutProtFltState) = 0.
0 = OFF
1 = ON

Parameter Number

53

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutNetFaultState

This parameter in conjunction with
Parameter 55 (OutNetFaultValue) defines
how the starter outputs will respond
on an Ethernet fault.
0 = GoToFaultValue
1 = HoldLastState

Parameter Number

54

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0