237

CIP Information

Appendix B

A single instance of the DPI Alarm Object will be supported.

The following common services will be implemented for the DeviceNet Interface
Object.

Attribute

ID

Access

Rule

Name

Data Type

Min/Max

Default

Description

15

Get/Set

Autobaud Enable

BOOL

0 -1

1

1= enabled; 0 = disabled

16

Get/Set

Consumed Assy

USINT

0 to 85

150 (drive 154)

See assembly instance definitions
for legal values

17

Get/Set

Produced Assy

USINT

100 to 190

151 (drive 155)

See assembly instance definitions
for legal values

19

Get/Set

Set to Defaults

BOOL

0 to 1

0

0=No action; 1=Reset

100

Get

Build

USINT

Firmware Build Number

101

Get

PTableinit errs

USINT

103

Get

Fan Data

Fan RPM
Fan Tach Pulses
Fan Control

Struct of

UINT
UINT
WORD

104

Get

Hardware Fault Data

Struct of

WORD

UINT

UINT

UINT

Bit0 = Forward Status
Bit1 = Reverse Status
Bit 2 = Disconnect On
Bit 3 = Brake Contactor
Bits 5-13 = unused
Bit 14 = CT Present error
Bit 15 = Power 24
Status Board Error
Present
Status Board Total Error
Present Conditions
Status Board Total Read
Errors

105

Get

Boot Rev

STRUCT of

USINT
USINT

Major rev
Minor rev

106

Get

NVS Object Init Errors

Struct of

UINT
Array of UINT

Number of Errors
List of CIP Objects that failed

107

Get

Error Data Structure

Struct of

DWORD
DWORD
DWORD

Service Code

Implemented for:

Service Name

Class Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single