Connection object, Class code 0x0005, Instance 190 – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 216

Advertising
background image

216

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Appendix B

CIP Information

Instance 190

Instance 190 is the 1999-ZCIO Native Format Produced Assembly.

Connection Object

CLASS CODE 0x0005

The following class attributes will be supported for the Connection Object.

14

Parameter 5 – DCBusVoltage

15

16

Parameter 11 – SwitchedVolts

OutputSourceV (IPS units)

17

18

Parameter 12 – UnswitchedVolts

SensorSourceV (IPS units)

19

20

Parameter 13 – InternalFanRPM

21

22

Parameter 14 – ElaspedRunTime

23

24

Parameter 15 – DriveTemperature

25

26

Parameter 16 – TripStatus

27

28

Parameter 17 – WarningStatus

29

30

Parameter 142 – DeviceValueKey

31

Instance 156 "Drive Status" – Produced Assembly for Bulletin 294E Starters

Instance 190 "Native 1" – DeviceLogix Consumed Assembly for Bulletin 294D Starters

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0 Pt04

Pt04

Pt03

Pt02

Pt01

Pt00

1 Ready

RunningReverse

RunningFoward

WarningPresent

TripPresent

2

Out05

Out04

Out03

Out02

Out01

Out00

RunReverse

RunFoward

3

JogReverse

JogForward

4

Pt07DeviceOut

Pt06DeviceOut

Pt05DeviceOut

Pt04DeviceOut

Pt03DeviceOut

Pt02DeviceOut

Pt01DeviceOut

Pt00DeviceOut

5

ZICCV (Low)

6

ZICCV (High)

Attribute ID

Access Rule

Name

Data Type

Value

1

Get Revision

UINT

2

Advertising