Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

105

Bulletin 290D/291D/294D Programmable Parameters

Chapter 4

Miscellaneous Configuration Group

Input05Function

This parameter determines the special
function for User Input 5:
0 = NoFunction
1 = FaultReset
2 = MotionDisable➊
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease➊

➊ These choices are level sensitive. All
others are edge sensitive

Parameter Number

63

Access Rule

GET/SET

Data Type

USINT

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

4

Default Value

0

NetworkOverride

This parameter allows for the local logic to
override a Network fault.
0 = Disable
1 = Enable

Parameter Number

64

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

CommsOverride

This parameter allows for local logic to
override an I/O connection timeout.
0 = Disable
1 = Enable

Parameter Number

65

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

KeypadMode

This parameter selects if the keypad
operation is maintained or momentary.
0 = Momentary
1 = Maintained

Parameter Number

66

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0