Bulletin 294d – Rockwell Automation 294D ArmorStart LT Distributed Motor Controller DeviceNet Version - User Manual User Manual

Page 182

Advertising
background image

182

Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

Chapter 6

Specifications

Bulletin 294D

Electrical Ratings

Power Circuit

Application

Three-phase

Number of Poles

3

Input Power Terminals

L1, L2, L3

Motor Power Terminals

T1, T2, T3

PE (Earth Ground) Terminal

4 PE terminals

Maximum Rated Operating Voltage

400Y/230…480Y/277 (-15%, +10%)

Rated Impulsed Voltage (U

imp

)

4 kV

Dielectric Withstand

UL: 1960V AC, IEC: 2500V AC

Operating Frequency

50/60 Hz (±10%)

Power Circuit

Maximum Rated

Operating Current

Cat. No.

Hp (kW)

Input Amps

400V AC, 50 Hz

Input Amps

480V AC, 60 Hz

Output Amps

294_-FD1P5*

0.5 (0.37)

2.0

1.8

1.5

294_-FD2P5*

1.0 (0.75)

3.7

3.0

2.5

294_-FD4P2*

2.0 (1.5)

6.5

5.5

3.6

Overload Protection

Solid-state I

2

T type

150% for 60 s or 200% for 3 s

Trip Class

Class 10 protection with speed sensitive response and power-down overload retention function

Overcurrent Protection

200% hardware limit, 300% instantaneous fault

Overvoltage Category

III

Reset Mode

Automatic or manual

Output Frequency

0…400 Hz (programmable)

Efficiency

97.5% typical

Overvoltage

380…480V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)

Undervoltage

380…480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)

Control Ride Through

Minimum ride through is 0.5 s — typical value is 2 s

Faultless Power Ride Through

10 ms

Carrier Frequency

2…10 kHz, drive rating based on 4 kHz

Speed Regulation — Open Loop

with Slip Compensation

±2% of base speed across a 40:1 speed range

Acceleration/Deceleration

Two independently programmable acceleration and deceleration times. Each time may

be programmed from 0…600 s, in 0.1 s increments.

Maximum Motor Cable Lengths (Reflected

Wave Protection) ➊

10 m (32 ft)(CE application)

14 m (45.9 ft) (non-CE application ➋)

Source Brake (EM Brake) Current

Maximum load current of 3 A

➊The reflected wave data applies to all frequencies 2…10 kHz.
➋ For CE compliant installations refer to the recommended EMI/RFI cord grip accessory. For availability of the quick disconnect three-phase shielded power and motor cable contact your local sales

representative for details.