187

Specifications

Chapter 6

EtherNet/IP

EtherNet/IP ODVA - Conformance Testing

EtherNet/IP Interoperability Performance – Per A9 PF 2.1

Ethernet Communication Rate

10/100 Mbps, half or full-duplex

Ethernet Ports

2 (embedded switch)

Ethernet Network Topologies Supported

Star, Tree, Linear, and Ring

Device Level Ring Support

Beacon Performance, IEEE 1583 Transparent Clock

Ethernet Connector

M12, D code, female, with Ethernet keying, 4 Pin

Ethernet Cable

Category 5e: Shielded or unshielded

IP Configuration

Static, DHCP, or BootP

DHCP Timeout

30 s

Data

Transported over both TCP and UDP

Packet Rate (pps)

500 packets-per-second (2000 μs), Tx

500 packets-per-second (2000 μs), Rx

Consume Instance (Command)

Default of 4 words (Instance 154)

Produce Instance (Status)

Default of 16 words (Instance 156)

Message Support

Unicast or Multicast

Address Conflict Detection (ACD)

IP v4 Address Conflict Detection for EtherNet/IP devices

Sockets

150 maximum

Web Server

Security

Login and password configurable

E-mail

Support Simple Mail Transfer Protocol (SMTP)

Webpage Features

Status, diagnostics, configuration

Concurrent Sessions

20

Web Server

HTTP 1.1

Network Connections

Concurrent TCP Connections

Maximum of 5 encapsulated messages over both TCP and UDP

Maximum I/O Connections (CIP Class 1)

Supports up to 2 Class 1 CIP connections [Exclusive owner (data) or

listen-only]. One connection per PLC. Listen-only connection

requires a data connection to be established.

Maximum Concurrent Explicit Messages (CIP Class 3)

6

Class 1 Connection API

2…3200 ms

Class 3 Connection API

100…10 000 ms

Request Packet Interval (RPI)

20 ms default (2 ms minimum)

Communication Ratings