Rockwell Automation Publication 290D-UM001A-EN-P - June 2012

85

Chapter

4

Bulletin 290D/291D/294D
Programmable Parameters

Electronic Data Sheet (EDS)

An embedded EDS file can be uploaded directly from the ArmorStart LT. EDS
files are also available on the internet at:

http://www.ab.com/networks/eds

.

Basic Setup Parameters

Table 19 lists the minimum setup configurations required for Bulletin 290D/
291D or Bulletin 294D.

RSLogix 5000 is the recommended commissioning software. Download the Add-
On-Profile (AOP) from

http://support.rockwellautomation.com/controlflash/Logix

Profiler.asp

for additional functionality. There are additional capabilities that are

not enabled or left at their default values.

Table 19 - Quick Parameter Setup

Bulletin 290D/291D

Bulletin 294D

28 FLASetting
29 OLResetLevel
30 OverloadClass
49 IOPointConfiguration

28 MotorNPVolts
29 MotorNPHertz
30 MotorOLCurrent
32 StopMode
34 MinimumFreq
35 MaximumFreq
36 AccelTime1
37 DecelTime1
49 IOPointConfiguration

IMPORTANT

All I/O points are configured as inputs, by default. Identify which points
are outputs, when needed for proper operation, using parameter 49
[IOPointConfiguration].