Appendix B

CIP Information

Instance 3

Instance 3 is the required output (consumed) assembly.

Instance 52

Instance 52 is the required input (produced) assembly.

Instance 100

Instance 100 is the Configuration Assembly for Bulletin 290D and 291D units.

101

Config

Configuration Assembly for Bulletin 294D Starters

150

Consumed

Default Consumed Instance for Bulletin 290D/291D units

154

Consumed

Default Consumed Instance for Inverter type units

155

Produced

Default Produced Instance for Inverter units

156

Produced

Exhaustive Produced Instance for Inverter type units

190

Produced

1999-ZCIO Native Format Produced Assembly

Instance Type

Description

Instance 3 "ODVA Cmd"

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Run Forward

Instance 52 "ODVA Status"

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

RunningForward

TripPresent

Instance 100 for 290D/291D Starters

Member Index

Byte Offset

Name

Parameter Instance

0

0

Reserved for Logix

N/A

1

2

AssemblyRevision

N/A

2

4

FLASetting

28

3

6

OLResetLevel

29

4

8

OverloadClass

30

5

10

ProtFltResetMode

41

6

12

ProtectFltEnable

42

7

14

WarningEnable

43

8

16

RunNetFltAction

45

9

18

RunNetFltValue

46

10

20

RunNetIdleAction

47

11

22

RunNetIdleValue

48

12

24

IOPointConfigure

49

13

26

FilterOffOn

50