5.2 Troubleshooting Message Communications

Message Communications Errors

5-32

Send Message Function (MSG-SNDE)

The parameters for the Send Message function are checked according to the following two communica-
tions protocols.
• Parameter List When Pro-Type (Communications Protocol) Is MEMOBUS

* IN: Input item
Note: Refer to the following manual for what to check in parameters 10 to 22 according to the protocol type that is being

used.

MP3000 Series Communications User’s Manual (Manual No.: SIEP C880725 12)

• Parameter List When Pro-Type (Communications Protocol) Is No-protocol 1 or No-protocol 2

* IN: Input item

Parameter

No.

IN/OUT

*

Item

Description and What to Check

10

IN

Connection number

Set the remote station to which to send the message. (Set the con-
nection number that is set in the connection parameters.)
Make sure that the setting is within the following setting range.
218IFD: 1 to 20

11

IN

Option

Specify the options. The meaning of this parameter depends on
the protocol.

12

IN

Function code

Set the function code to send.

14

IN

Remote data
address, lower word

Set the register address to read or write at the remote station.
(Specify the word address to access registers, and specify the bit
address to access relays or coils.)

15

IN

Remote data
address, upper word

16

IN

Remote station reg-
ister type

Set the register type to read or write at the remote station.

17

IN

Data size

Set the size of the data to read or write. (Specify the size in words
for registers, and in bits for relays or coils.)

18

IN

Remote CPU mod-
ule number

Set the CPU number at the remote station.

20

IN

Local data address,
lower word

Set the data address to store read data or write data in the local
station. (Specify the word address to access registers, and specify
the bit address to access relays or coils.)

21

IN

Local data address,
upper word

22

IN

Local station regis-
ter type

Set the register type to store read data or write data in the local
station.

Parameter

No.

IN/OUT

*

Item

Description and What to Check

10

IN

Connection number

Set the remote station to which to send the message. (Set the con-
nection number that is set in the connection parameters.)
Make sure that the setting is within the following setting range.
218IFD: 1 to 20

11 to 16

Not used.

17

IN

Data size

Set the size of the data to write. (Specify the size in words for No-
protocol 1, and in bits for No-protocol 2.)

18

Not used.

20

IN

Local data address,
lower word

Set the data address to store write data in the local station.

21

IN

Local data address,
upper word

22

IN

Local station regis-
ter type

Set the register type of the write data to store in the local station.