8.1 MP3200 Battery Replacement

8-4

8.

Press the connector back into the CPU Unit.

9.

Hold the connector, and while pressing it toward the CPU Unit’s internal circuit board (the board
on the side of the clamp), move the Battery and the battery holder into the CPU Unit.

Note: If this procedure is not followed, the battery leads may pinched between the Battery and the circuit board,

causing stress on the leads. If that occurs, the battery holder will bulge after step 8 of the procedure.

10.

Close the battery holder and confirm that the BAT indicator on the CPU Unit is not lit.

This concludes the Battery replacement procedure.

Press in.

2 battery leads

CPU Unit internal circuit board
(on the side of the clamp)

Move the Battery.

Clamp

Lit.

Not lit.