2.2 CPU Unit/CPU Module Indicators and Display

Display

2-10

E061:
Unit configuration
error

There is a configuration
error on Rack .
: 1 to 7

Check the following con-
ditions.
• There are more than

three MP3000 Units.

• There is more than one

MP2000 Unit.

• There is more than one

Sub CPU.

• There are more than two

Base Units.

• An MP2000 Unit is

mounted to Rack 5 to 7
(excluding to the right of
a Sub CPU).

• More than one EXIOIF

Module is mounted.

• An EXIOIF Module is

mounted under a Sub
CPU.

Correct the Unit con-
figuration.

E062:
Unit configuration
error

E063:
Unit configuration
error

E064:
Unit configuration
error

E065:
Unit configuration
error

E066:
Unit configuration
error

E067:
Unit configuration
error

E070:
Unsupported Sub
CPU mode

A CPU version that does
not support operation as a
Sub CPU was mounted as
a Sub CPU.

Check the system soft-
ware version.

Use a version of the
CPU that supports
operation as a Sub
CPU.

E071:
Unsupported Module
detected

 

A Module that cannot be
used was mounted.

Check to see if the Mod-
ules are supported.

Remove any Modules
that are not supported.

E080:
CPU mode mismatch

The Main CPU contains a
Sub CPU project.
Or a Sub CPU contains a
Main CPU project.

Log on from the MPE720
and check the Module con-
figuration definitions.

Transfer a Main CPU
project to the Main
CPU. Transfer a Sub
CPU project to the
Sub CPU.

E081:
CPU stopped for
internal temperature
error 1

 

The temperature contin-
ued to increase even fur-
ther after A241 was
detected and is approach-
ing the permissible tem-
perature of the internal
parts.

Check SB00041F (tem-
perature warning).

Change the installa-
tion environment to
lower the temperature
around the CPU.
If the CPU tempera-
ture increases and an
error occurs, turn OFF
the power supply to
the Controller and
change the installa-
tion environment.

E082:
CPU stopped for
internal temperature
error 2

 

The temperature contin-
ued to increase even after
E081 was detected and has
reached the permissible
temperature of the internal
parts.

E083:
Fan stopped (1 min-
ute)

The Fan stopped continu-
ously for 1 minute.

Check to see if the Fan is
operating.
Or, check SB00041E (Fan
error).

Check the Fan opera-
tion.
If the Fan is not oper-
ating, turn OFF the
power supply to the
Controller and replace
the Fan.

Continued on next page.

Continued from previous page.

Alarm Code

Alarm Name

MP3200

MP3300

Cause

Confirmation Method

Correction