Yaskawa MP3200 Troubleshooting Manual User Manual

Page 154

Advertising
background image

7.5 System Register Configuration and Error Status

Error Status for Individual Products

7-28

265IF-01 Error Status

Table 7.11 EtherCAT-S Error Status Details

Item

Code

Remarks

Error code

0

No error

1

Station error

Communications phase

0

Non-INIT

1

INIT

2

PRE-OPERATIONAL

3

SAFE-OPERATIONAL

4

OPERATIONAL

Data valid flags

Bit 0

0: Process data not communicated
1: Process data communications in progress

Bit 1 to Bit F

Reserved.

(CompoNet-M)

F

8 7

0 (Bit number)

SW00 + 0

Error code (station error = 1)

Subslot (function) number (= 1)

SW00 + 1

Reserved.

SW00 + 2

Communications status flags

SW00 + 3

Module status code

SW00 + 4

Network status code

SW00 + 5

Not used.

SW00 + 6

Not used.

SW00 + 7

Not used.

Table 7.12 CompoNet-M Error Status Details

Item

Code

Remarks

Error code

0

No error

1

Station error

Communications status
flags

Bit 0

0: Communications error or no communications
1: All communications normal

Bit 1

0: No slave communications error
1: Slave communications error

Bit 2

0: No repeater communications error
1: Repeater communications error

Bit 3 to

Bit F

Reserved.

Module status code

0

1

2

Normal

3

Minor error

4

Fatal error

Continued on next page.