3.2 Troubleshooting Errors with the System Monitor

Investigating I/O Errors

3-9

T

roubleshooting using the System Monitor

The following procedure will outline the corrective action to take using the following example: an Output
Error in the SVC Function Module (rack 1, slot 0).

1.

Check the description of the error message and click the OK Button.
The Status Area in the System Monitor Dialog Box will give information on the I/O Module where the
error occurred.

2.

Confirm the rack and slot information, then set the system register addresses from SW00208 to
SW00215 in the register list and check the contents.
Refer to the following section for details on system I/O error status.

7.5 System Register Configuration and Error Status

System I/O Error Status (page 7-15)