7.5 System Register Configuration and Error Status

User Operation Error Status in Ladder Programs

7-12

User Operation Error Code -1: Operation Errors

* The numeric values given in brackets [ ] are set by the system in the Changed A Register or Changed F Register before the oper-

ation error drawing is executed.

Error Code

Error Description

Operation When an Error Occurs

Inte

ger Op

era

tions

0001 hex

Integer operation underflow

[-32768]

0002 hex

Integer operation overflow

[32767]

0003 hex

Integer operation division error

[The A register stays the same.]

0009 hex

Double-length integer operation underflow

[-2147483648]

000A hex

Double-length integer operation overflow

[2147483647]

000B hex

Double-length integer operation division error [The A register stays the same.]

000C hex

Quadruple-length integer operation underflow [-9223372036854775808]

000D hex

Quadruple-length integer operation overflow

[9223372036854775807]

000E hex

Quadruple-length integer operation division
error

[The A register stays the same.]

0101 hex to

010E hex

Integer operation error in Operation Error
Drawing

[The A register stays the same.]

Re

al N

umber Op

era

tions

0010 hex

Non-numerical integer storage error

Data is not stored. [00000]

0011 hex

Integer storage underflow

Data is not stored. [-32768]

0012 hex

Integer storage overflow

Data is not stored. [+32767]

0021 hex

Real number storage underflow

Data is not stored. [-1.0E+38]

0022 hex

Real number storage overflow

Data is not stored. [1.0E+38]

0023 hex

Real number operation division by zero error

Data is not stored. [F register stays the
same]

0030 hex

Invalid real number operation (non-numeric)

Data is not stored.

0031 hex

Real number operation exponent underflow

0.0

0032 hex

Real number operation exponent overflow

Maximum value

0033 hex

Real number operation division error (0/0)

Operation is not executed.

0034 hex

Real number storage exponent underflow

Stores 0.0.

0040 hex

to

0059 hex

Real number operation error in standard sys-
tem function

Operation is aborted and output is set to 0.0.

0040 hex: SQRT

0047 hex: EXP

004E hex: PD

0055 hex: SLAU

0041 hex: SIN

0048 hex: LN

004F hex: PID

0056 hex: REM

0042 hex: COS

0049 hex: LOG

0050 hex: LAG

0057 hex: RCHK

0043 hex: TAN

004A hex: DZA

0051 hex: LLAG

0058 hex: BSRCH

0044 hex: ASIN

004B hex: DZB

0052 hex: FGN

0059 hex: SORT

0045 hex: ACOS

004C hex: LIM

0053 hex: IFGN

0046 hex: ATAN

004D hex: PI

0054 hex: LAU