Do-01 error status – Yaskawa MP3200 Troubleshooting Manual User Manual

Page 157

Advertising
background image

7.5 System Register Configuration and Error Status

Error Status for Individual Products

7-31

T

roubleshooting System Errors

Valid Ranges for AI/AO Adjustment Values

Offset: -9,999 to 9,999

Gain: 0.0001 to 1.9999

DO-01 Error Status

Table 7.15 MIXIO Error Status Details

Item

Code

Remarks

Error code

0

No error

2

I/O Error

FLT

0

Oscillator and ASIC for AO are normal.

1

Oscillator error or error in ASIC for AO

FUSE

0

Fuse normal

1

Fuse error

ADJI

0

AI shipping adjustment value normal

1

AI shipping adjustment value not set or
adjustment value error

ADJO

0

AO shipping adjustment value normal

1

AO shipping adjustment value not set or
adjustment value error

Table 7.16 CNTR-A Error Status Details

Item

Code

Remarks

Error code

0

No error

2

I/O Error

FLT

0

Counter ASIC normal

1

Counter ASIC error

PA

0

Phase A normal

1

Phase A disconnection detected

PB

0

Phase B normal

1

Phase B disconnection detected

(DO)

F

8 7

0 (Bit number)

SW00 + 0

Error code (I/O error = 2)

Subslot (function) number (= 1)

SW00 + 1

Not used.

SW00 + 2

Not used.

SW00 + 3

Not used.

SW00 + 4

Not used.

SW00 + 5

Not used.

SW00 + 6

Not used.

SW00 + 7

Not used.

Advertising