2 troubleshooting errors with the system monitor, System errors, System errors -3 – Yaskawa MP3200 Troubleshooting Manual User Manual

Page 43

Advertising
background image

3.2 Troubleshooting Errors with the System Monitor

System Errors

3-3

T

roubleshooting using the System Monitor

3.2

Troubleshooting Errors with the System Monitor

This section describes how to troubleshoot errors caused by the Machine Controller system, as well as
scan time exceeded errors, operation errors, and I/O errors.

System Errors

If one or more of the following errors appear in the System Monitor Dialog Box, a system error has
occurred in the Machine Controller.

Error Displayed in System

Monitor Dialog Box

Meaning of Error

Correction

The ALM indicator is lit red.

The Machine Controller has a system
error and cannot enter Run Mode.

Check SB000402 to identify and correct
the source of the error.

The ERR indicator is lit red.

An operation error or I/O error has
occurred.

Check SB000403 to identify and correct
the source of the error.

The BAT indicator is lit red.

The Battery replacement period has
come.

Replace the Battery. Refer to the follow-
ing chapter for Battery replacement pro-
cedures.

Chapter 8 MP3200/MP3300 Battery
Replacement