7.5 System Register Configuration and Error Status

USB-related System Status

7-16

USB-related System Status

The data in these registers give information on the USB memory and give the error status.

Message Relaying Status

The data in these registers give the status of the command or response in the message function.

Name

Register Addresses

Remarks

Available USB Memory

SL00650

Unit: Kilobytes

Total USB Memory

SL00652

USB Status

SW00654

SB006540

0: No USB memory device
1: USB memory device inserted

SB006541

0: Not supplying power
1: Supplying power

SB006542

0: Cannot recognize USB memory device
1: Recognized USB memory device

SB006543

0: Not accessing USB memory device
1: Accessing USB memory device

SB006544

0: -
1: Checking FAT file system

SB006545 to
SB00654F

Reserved for system.

FAT Type

SW00655

0002 hex FAT16
0003 hex FAT32

Reserved for system.

SW00656 and SW00657

Batch Load and Batch
Save

SW00658

SB006580

1: Batch load in progress

SB006581

1: USB memory read error

SB006582

1: Load file model mismatch error

SB006583

1: Load file write error

SB006584

1: Save to flash memory error

SB006585

1: Folder for batch loading does not exist

SB006586

1: Loading error due to program write protection

SB006587

Reserved for system.

SB006588

1: Batch save in progress

SB006589

1: USB memory write error

SB00658A

1: Save file read error

SB00658B

1: Security error

SB00658C to
SB00658F

Reserved for system.

Reserved for system.

SW00659

Name

Register Address

Description

Message Relaying
Information

SW00694

Normally processed command message counter

SW00695

Command message error counter

SW00696

Normally processed response message counter

SW00697

Response message error counter

Advertising