5.2 Troubleshooting Message Communications

Message Communications Errors

5-24

Checking the Processing Result (PARAM00) for the Receive Message Function (MSG-
RCVE)

The errors that may be given by the processing result of the Receive Message function are listed in the fol-
lowing table.
• Processing Results Other Than a Communications Section Error (88 Hex)

Processing

Result

Value

Error

Cause

Correction

81 hex

Function code
error

An unused function code was received
from a remote station.

Check whether the remote station sent
valid data.

82 hex

Address set-
ting error

Data for an address that is outside of the
setting range was received from the
remote station.

Check whether the remote station sent
valid data.

One of the following settings is outside of
the setting range.
PARAM14 and PARAM15
(remote data address)
PARAM20 and PARAM21
(local data address)

Check the settings that are given on
the left.

83 hex

Data size
error

The receive data size from the remote sta-
tion is outside of the setting range.

Check whether the remote station is
sending data of a valid size.

84 hex

Circuit num-
ber setting
error

The circuit number is outside of the set-
ting range.

Check Cir-No (circuit number) in
MSG-RCVE.
The device may be set incorrectly.
Also check the communications
device type (Dev-Typ) in the MSG-
RCVE function.

85 hex

Channel num-
ber setting
error

The communications buffer channel num-
ber is outside of the setting range.

Check Ch-No (communications buffer
channel number) in MSG-RCVE.

86 hex

Connection
number error

The connection number is outside of the
setting range.

Check PARAM10 (connection num-
ber).

89 hex

Device select
error

An unavailable device is set.

Check Dev-Typ (communications
device type) in MSG-RCVE and
select the appropriate device type.

C0 hex

Register type
error

The register type specified by the remote
(sending) station is out of range.

Check the register type for the remote
station specified at the local station
and set the correct register type.

C1 hex

Data type
error

The data type is outside of the setting
range. This error occurs when using func-
tion code 434D hex or 434E hex.

Check the remote address table set at
the sending station and set the correct
data type.