Message communications errors, Message communications errors -14, Checking the error status and transmission status – Yaskawa MP3200 Troubleshooting Manual User Manual

Page 89: Error status box = 0: no error

Advertising
background image

5.2 Troubleshooting Message Communications

Message Communications Errors

5-14

Message Communications Errors

This section describes errors that can occur in message communications.

Checking the Error Status and Transmission Status

If message communications with a PLC, touch panel, or PC from another manufacturer do not start, get a
general idea of the error in the status information in the Module’s Detail Definition Dialog Box on the
MPE720.

Error Status Box = 0: No error

Get a general idea of the error by referring to the Trans Status Column.

When the TCP Protocol Is Selected

Trans Status

(Transmission

Status)

Status

Cause

Correction

Reference

- - - - -

Message
communica-
tions are not
set.

Connection parameters have
not been set.

Set the connection parame-
ters.

Checking the
Connection
Parameters (page
5-17)

The data was not saved to
flash memory or the power
supply to the Module was not
turned OFF and ON again
after changing the connection
parameters.

Save the data to flash mem-
ory and turn the power sup-
ply OFF and ON again to the
Module after setting connec-
tion parameters.

IDLE

Standby
mode for
executing
message
functions.

No message functions have
been created in the ladder pro-
gram.

Create message functions in
the ladder program.

Checking Mes-
sage Functions
(MSG-SNDE and
MSG-RCVE)
(page 5-20)

Message functions have been
created in the ladder program
but they have not been exe-
cuted.

Create and execute message
functions in the ladder pro-
gram.

There is an error in a message
function parameter setting
(PARAM).

Set the message function
parameter (PARAM)
correctly.

WAIT

Waiting for
establish-
ment of TCP
connection
with the
remote
device

The remote device is not con-
nected or the power to the
remote device is OFF.

Connect the remote device
and turn ON the power to
the remote device.

The remote device does not
have a communications func-
tion or setting for communi-
cating with the Machine
Controller or there is an error
in communications settings.

Check the communications
function or setting and the
communication settings of
the remote device.

There is an error in the con-
nection parameter settings in
the Machine Controller.

Check the connection
parameter settings in the
Machine Controller.

Checking the
Connection
Parameters (page
5-17)

Continued on next page.

Advertising