Yaskawa MP3200 Troubleshooting Manual User Manual

Page 153

Advertising
background image

7.5 System Register Configuration and Error Status

Error Status for Individual Products

7-27

T

roubleshooting System Errors

263IF-01 Error Status

264IF-01 Error Status

(EtherNetIP)

F

8 7

0 (Bit number)

SW00+ 0

Error code (station error = 1)

Subslot (function) number (= 1)

F

0

(Bit number)

SW00 + 1

CNO

#16

···························

CNO#1

SW00 + 2

ST#32

···························

ST#17

SW00 + 3

ST#48

···························

ST#33

SW00 + 4

ST#64

···························

ST#49

SW00 + 5

Not used.

SW00 + 6

Not used.

SW00 + 7

Not used.

Table 7.10 EtherNet/IP Error Status Details

Item

Code

Remarks

Error code

0

No error

1

Station error

CNO#n

0

Communications normal

1

Communications error at station n

(EtherCAT-S)

F

8 7

0 (Bit number)

SW00 + 0

Error code (station error = 1)

Subslot (function) number (= 1)

(Bit number)

SW00 + 1

Reserved.

SW00 + 2

Communications error code

SW00 + 3

Communications phase

SW00 + 4

Data valid flags

SW00 + 5

Not used.

SW00 + 6

Not used.

SW00 + 7

Not used.

Advertising